Prolink PRO903-ES/EL 3KVA

PROLiNK Professional II+ Series (1P/1P) is a single-phase UPS system using microprocessor controlled true online double conversion technology and it can be used to provide protection for critical loads especially on IT applications. High input power factor correction in the system improves efficiency and reduces overall losses.

Description

UPS Type
Tower
Phase
Single phase with ground
Rating (VA)
3000
Nominal Power (W)
2700
Standard Model
Dimension (mm)
421 x 190 x 318 (D x W x H)
Weight (kg)
27.6
Long-run Model
Dimension (mm)
397 x 145 x 220 (D x W x H)
Weight (kg)
7.4
INPUT
Connection Type
IEC 320-C20
Nominal Voltage
200/208/220/230/240 VAC
Voltage Range
110-300 VAC (Load at 50%)
160-280 VAC (Load at 100%)
Frequency Range
45 ~ 70 Hz
Power Factor
>= 0.99
OUTPUT
Connection Type
4 x Universal socket (PRO903ES)
2 x Universal socket (PRO903EL)
Terminal
Nominal Voltage
200/208/220/230/240 VAC
Voltage Regulation
±1%
Frequency Range (Synchronized Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio
3:1
Harmonic Distortion
≤3% THD (Linear load)
≤6% THD (Non-linear load)
ALARM & INDICATORS
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
LCD
Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault
CONNECTIVITY, CONTROL & MONITORING
Front panel
Status LED, Function keys, LCD display
Communication
Smart RS232*
USB Port
BATTERY
Standard Model
Type
12V / 9Ah
Numbers
6
Typical Recharge Time
4 hours recover to 90% capacity
Long-run Model
Depending on the capacity of external batteries
Number
6
Charging Current (max)
1A / 2A / 4A / 6A Adjustable
REAR PANEL
1. AC Input
2. Input circuit breaker
3. USB Communication port
4. RS-232 communication port
5. Intelligent slot
6. External battery connection (Only available for L model)
7. Output receptacles
8. Output circuit breaker