Prolink PRO801-QS 1KVA

Master II Series (1P/1P)

PROLiNK Master II Series (1P/1P) Tower Type is a new UPS system series with output power factor 1.0. The UPS design is using true online double-conversion technology which provides higher charging current and it can be set via LCD display. The system is designed to provide protection for critical loads such as sensitive networks, small computer centres, servers, medical equipment, telecom applications as well as industrial applications. High input power factor correction in the system improves the efficiency and reduces overall losses.

Description

GENERAL

UPS Type Tower
Phase Single phase with ground
Rating (VA) 1000
Nominal Power (W) 1000
Dimension (mm) 397 x 145 x 220 (D x W x H)
Weight (kg) 13 (with battery)6.6 (without battery)

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Based on load at 50%)160-300 VAC (Based on load at 100%)
Frequency Range 40 Hz ~ 70 Hz
Power Factor ≧0.99
THDi ≦ 5%

OUTPUT

Connection Type 4 x IEC 320-C13
Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47~53 Hz or 57~63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦2% THD (Linear load)≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*USB Port

Emergency Power Off (EPO)

BATTERY

Type 12V / 7Ah
Numbers 3
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 12A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan