Prolink PRO801-ERS/ERL 1KVA Rack/Tower

Master II Series (1P/1P) – Rack/Tower

PROLiNK Master II Series (1P/1P) Rack / Tower Type is a true online double conversion single phase UPS system
which is designed to deliver clean and high quality electrical power to fully protect critical devices in wide range of
applications. High input power factor correction in the system improves the efficiency and reduces overall losses.

Description

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 1000
Nominal Power (W) 900
Standard ModelDimension (mm) 410 x 438 x 88 [2U] (D x W x H)
Weight (kg) 11.6
Long-run ModelDimension (mm) 410 x 438 x 88 [2U] (D x W x H)
Weight (kg) 6.4

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 55-150 VAC ± 5%110-300 VAC ± 5%
Frequency Range 40Hz ~ 70Hz
Power Factor ≧0.99

OUTPUT

Connection Type 8 x IEC 320-C13
Nominal Voltage 200/208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.5% or 60Hz ± 0.5%
Current Crest Ratio 5:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*USB Port

Emergency Power Off (EPO)

BATTERY

Standard ModelType 12V / 9Ah
Numbers 2
Typical Recharge Time  4 hours recover to 90% capacity
Long-run ModelType Depending on the capacity of external batteries
Numbers Depending on the capacity of external batteries
Charging Current (max) 1A / 2A / 4A / 8A

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Input circuit breaker
  5. Network/Fax/Modem surge protection
  6. Emergency power off function connector (EPO)
  7. USB communication port
  8. RS-232 communication port
  9. Intelligent slot
  10. External battery connection
  11. Cooling fan